TY - JOUR
T1 - Development of an evidence-based methodological framework for overheating risk assessment of higher education buildings
T2 - occupant-centric retrofitting design strategies
AU - Chaer, Issa
AU - Ozarisoy, Bertug
AU - Elnour Ismail, Mubarak Abdelrasoul
PY - 2026/1/15
Y1 - 2026/1/15
N2 - This study investigates overheating and indoor air quality in an eight-storey, atrium-type higher-education building in London. High glazing ratios and dense occupancy were hypothesised to assess overheating risk and CO2 concentrations. A mixed-methods framework combined 10-minute environmental monitoring between July 2024 and April 2025 with a calibrated building energy simulation model. Thermal comfort was assessed using TM59 and EN 16798, and IAQ via BB101 thresholds; field data informed schedules, gains, and ventilation for model calibration. Summer indoor temperatures peaked at 30 °C; mean daily maxima and minima were at 24.69 °C (SD 2.57) and 22.56 °C. Across 120 occupied hours, 5.0 % (6 h) were > 28 °C (TM59 limit: 3 %), while DWE remained ≤ 6. Winter–spring studios met TM59 (0 % hours > 28 °C; DWE = 0). CO2 levels typically ranged 900–1,300 ppm, consistently < 1,500 ppm but frequently above a 1,000 ppm “good” target. The study findings indicate that solar gains and internal loads as primary drivers. Recommended measures are external shading, controlled night-purge, timed pre-class/break purges, CO2-based demand-controlled ventilation (900–1,000 ppm setpoint), internal gain reduction, and targeted peak-shaving mechanical cooling, prioritised and validated through calibrated evidence-based retrofit design strategies for TM59/BB101 compliance.
AB - This study investigates overheating and indoor air quality in an eight-storey, atrium-type higher-education building in London. High glazing ratios and dense occupancy were hypothesised to assess overheating risk and CO2 concentrations. A mixed-methods framework combined 10-minute environmental monitoring between July 2024 and April 2025 with a calibrated building energy simulation model. Thermal comfort was assessed using TM59 and EN 16798, and IAQ via BB101 thresholds; field data informed schedules, gains, and ventilation for model calibration. Summer indoor temperatures peaked at 30 °C; mean daily maxima and minima were at 24.69 °C (SD 2.57) and 22.56 °C. Across 120 occupied hours, 5.0 % (6 h) were > 28 °C (TM59 limit: 3 %), while DWE remained ≤ 6. Winter–spring studios met TM59 (0 % hours > 28 °C; DWE = 0). CO2 levels typically ranged 900–1,300 ppm, consistently < 1,500 ppm but frequently above a 1,000 ppm “good” target. The study findings indicate that solar gains and internal loads as primary drivers. Recommended measures are external shading, controlled night-purge, timed pre-class/break purges, CO2-based demand-controlled ventilation (900–1,000 ppm setpoint), internal gain reduction, and targeted peak-shaving mechanical cooling, prioritised and validated through calibrated evidence-based retrofit design strategies for TM59/BB101 compliance.
UR - https://doi.org/10.1016/j.enbuild.2025.116723
U2 - 10.1016/j.enbuild.2025.116723
DO - 10.1016/j.enbuild.2025.116723
M3 - Article
SN - 0378-7788
VL - 351
JO - Energy and Buildings
JF - Energy and Buildings
M1 - 116723
ER -