TY - JOUR
T1 - Investigating the influence of outdoor temperature variations on fire-induced smoke behavior in an atrium-type underground metro station using hybrid ventilation systems
AU - Xu, Desheng
AU - Li, Yanfeng
AU - Du, Tianmei
AU - Zhong, Hua
AU - Huang, Youbo
AU - Li, Lei
AU - Xiangling, Duanmu
N1 - Publisher Copyright:
© 2023
PY - 2023/11/5
Y1 - 2023/11/5
N2 - Underground metro systems are expanding rapidly worldwide, necessitating research on energy-efficient ventilation systems, fire safety, and smoke control. This study investigates the optimisation of hybrid mechanical-natural ventilation for smoke control in complex metro stations. Full-scale winter/summer experiments and numerical simulations examined a double-deck atrium-type station. Results demonstrate the atrium fires are more significantly impacted by outdoor temperature variations versus concourse/platform fires, with a 70 K versus 30 K temperature rise above the fire respectively. The heat of the gathered high-temperature smoke inside the atrium can reach up to 900 K under a 5 MW train fire energy release. The dimensionless Archimedes number (Ar) defines the ratio of thermal buoyancy to gravitational forces. Cold exterior winter air (Ar<1) entering via the atrium ceiling openings restricted vertical smoke diffusion, enabling enhanced lateral propagation. With rising outdoor temperatures from −20 °C to 10 °C (Ar<1), the natural smoke extraction efficiency increased from 0 to 18 %, coupled with vertical airflow velocities accelerating from −3.5 m/s to 1.5 m/s. When outdoor temperatures were between 10 °C and 40 °C (Ar>1), airflow velocity only changed slightly. Empirical models predict internal temperature profiles as a function of external meteorology. The findings provide crucial engineering insights into integrating weather data and adaptable ventilation protocols for scenario-based smoke prevention/mitigation. Further work should examine seasonal variations beyond the tested -20‒40 °C range. Overall, considering outdoor climate effects allows 30 % optimisation of hybrid ventilation systems for fire safety in underground metro stations. This study promotes technological advances in energy-efficient transport infrastructure resilience.
AB - Underground metro systems are expanding rapidly worldwide, necessitating research on energy-efficient ventilation systems, fire safety, and smoke control. This study investigates the optimisation of hybrid mechanical-natural ventilation for smoke control in complex metro stations. Full-scale winter/summer experiments and numerical simulations examined a double-deck atrium-type station. Results demonstrate the atrium fires are more significantly impacted by outdoor temperature variations versus concourse/platform fires, with a 70 K versus 30 K temperature rise above the fire respectively. The heat of the gathered high-temperature smoke inside the atrium can reach up to 900 K under a 5 MW train fire energy release. The dimensionless Archimedes number (Ar) defines the ratio of thermal buoyancy to gravitational forces. Cold exterior winter air (Ar<1) entering via the atrium ceiling openings restricted vertical smoke diffusion, enabling enhanced lateral propagation. With rising outdoor temperatures from −20 °C to 10 °C (Ar<1), the natural smoke extraction efficiency increased from 0 to 18 %, coupled with vertical airflow velocities accelerating from −3.5 m/s to 1.5 m/s. When outdoor temperatures were between 10 °C and 40 °C (Ar>1), airflow velocity only changed slightly. Empirical models predict internal temperature profiles as a function of external meteorology. The findings provide crucial engineering insights into integrating weather data and adaptable ventilation protocols for scenario-based smoke prevention/mitigation. Further work should examine seasonal variations beyond the tested -20‒40 °C range. Overall, considering outdoor climate effects allows 30 % optimisation of hybrid ventilation systems for fire safety in underground metro stations. This study promotes technological advances in energy-efficient transport infrastructure resilience.
KW - Fire energy release
KW - Atrium-type underground metro station
KW - Hybrid ventilation systems
KW - Smoke extraction efficiency
KW - Fire safety
UR - http://dx.doi.org/10.1016/j.energy.2023.129570
U2 - 10.1016/j.energy.2023.129570
DO - 10.1016/j.energy.2023.129570
M3 - Article
SN - 0360-5442
VL - 287
SP - 129570
JO - Energy
JF - Energy
M1 - 129570
ER -