Abstract
Indoor substations are critical for electrical infrastructure, but insufficient ventilation induces severe transformer heat accumulation, impairing their performance and service life. This study uses computational fluid dynamics (CFD) to analyze and optimize the thermal environment in a typical 110 kV indoor substation. Initial assessments of two existing ventilation systems (natural intake with mechanical exhaust, full natural ventilation) reveal extremely low efficiency, dominated by cold air short-circuiting. In the baseline scenario, 55.7% of intake air bypasses heat-generating transformers directly, with no effective heat exchange. Three optimization strategies were proposed and simulated: sealing short-circuiting vents (0.5°C max transformer temperature reduction); adding basement guide vanes (additional 2.7°C reduction); and deploying a novel air duct system with optimized flow rates and directional outlets). The combined air duct and guide vane scheme performs best: it reduces peak transformer temperature by up to 23.9°C relative to the baseline, and 3°C lower than the duct system alone, with efficient cooling air utilization. Optimizing airflow paths for heat source contact outperforms increasing undirected airflow, providing a core design principle for substation ventilation optimization. This study provides validated, practical design strategies for enhanced transformer heat dissipation and indoor substation thermal resilience, suitable for both substation retrofits and new builds.
| Original language | English |
|---|---|
| Article number | 142027 |
| Journal | Energy |
| Volume | 361 |
| Early online date | 24 Jul 2026 |
| DOIs | |
| Publication status | Published - 1 Oct 2026 |
Funding
This work was supported by the National Natural Science Foundation of China (Grant No. 52506029).
| Funders | Funder number |
|---|---|
| National Natural Science Foundation of China | 52506029 |
Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver