Performance analysis for the UK's first 5th generation heat network – The BEN case study at LSBU

A. Gillich, J. Godefroy, A. Ford, M. Hewitt, J. L'Hostis

Research output: Contribution to journalArticlepeer-review

17 Citations (Scopus)

Abstract

The decarbonisation of heat requires a transition from gas boilers to low-carbon heating systems such as heat pumps. Efficiency gains can be achieved by linking heating systems through ambient loops called Fifth Generation District Heating and Cooling (5GDHC) networks. The UK needs working demonstrators to understand both the technical and practical challenges in the heat transition. The Balanced Energy Network (BEN) links two buildings on LSBU's campus and is the UK's first 5GDHC system at scale and among the first in the world to be retrofit in parallel to an incumbent gas system and include an active demand side response control system to toggle between energy vectors in way that minimises cost and carbon emissions. This paper presents performance data from its first year of operation in baseline mode, as it was commissioned and optimised. High temperature heat pumps were retrofit to an existing gas boiler circuit and match the 79 °C output temperature of the gas boiler system. No fabric upgrades were required and no pipes, ducts or heat emitters were resized, however the system maintained performance to reduce overall building carbon emissions by 13% and gas use by 40% across both buildings compared to the pervious heating season while the system was in use.
Original languageEnglish
Article number122843
JournalEnergy
Volume243
DOIs
Publication statusPublished - 21 Dec 2021

Fingerprint

Dive into the research topics of 'Performance analysis for the UK's first 5th generation heat network – The BEN case study at LSBU'. Together they form a unique fingerprint.

Cite this